8496

Overvoltage or Undervoltage Detected

ABB · AC500

Hva betyr 8496 ?

The Safety PLC has detected an abnormal power supply condition, specifically either an overvoltage or undervoltage. This issue can stem from an unstable power source, incorrect wiring, or a fault within the PLC's internal power conditioning circuitry. Prolonged exposure to incorrect voltage can damage the PLC or cause erratic behavior, compromising safety.

Vanlige årsaker

  • Faulty or improperly regulated 24VDC power supply unit feeding the safety PLC, providing voltage outside the specified range (e.g., 21.6V-26.4V).
  • Loose or corroded power supply wiring to the safety PLC's L+ and M terminals, causing significant voltage drop (undervoltage).
  • High current draw from other devices on the same 24VDC bus causing the voltage to sag below the PLC's minimum threshold.
  • External electrical disturbances (e.g., motor starting, welding equipment) causing temporary voltage spikes (overvoltage) or dips (undervoltage).
  • Incorrect fusing or circuit breaker tripping intermittently, leading to momentary power loss or reduced voltage.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure the 24VDC power supply voltage directly at the safety PLC's L+ and M input terminals using a calibrated multimeter, checking for overvoltage (e.g., >26.4V) or undervoltage (e.g., <21.6V).

  2. 2

    Inspect all power cabling, including terminal blocks and wire connections, leading to the safety PLC for loose connections, corrosion, or damage.

  3. 3

    Verify the output voltage of the 24VDC power supply unit under load and ensure it is stable and within its specified operating range.

  4. 4

    Isolate the safety PLC by temporarily disconnecting other loads from the 24VDC power supply to check if the voltage stabilizes.

  5. 5

    Check for external sources of electrical interference or voltage fluctuations on the main supply grid that might be affecting the 24VDC power supply.

  6. 6

    Replace the 24VDC power supply unit if it fails to maintain stable voltage within the safety PLC's specified operating range.