Oversetter...
2211

Current Measurement Transformer Failure

ABB · ACS560 Standard Control Program Firmware

Hva betyr 2211 ?

A failure has occurred in the current transformer within the output current measurement circuit. This means the drive cannot accurately monitor motor current, which is critical for protection and control, potentially leading to motor or drive damage if operation continues without proper current feedback.

Vanlige årsaker

  • Damaged current transformer (CT) coil or core due to mechanical shock or overcurrent events.
  • Loose or corroded connections in the CT secondary circuit to the control board.
  • Internal fault on the drive's control board affecting the current measurement input circuitry.
  • Output phase imbalance causing abnormal current distribution and CT stress.
  • Incorrect motor parameters (e.g., P03-03 Motor Rated Current) leading to misinterpretation of CT signals.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    De-energize the drive and visually inspect the current transformers for signs of physical damage (e.g., cracks, burnt insulation).

  2. 2

    Check all wiring connections from the current transformers to the drive's control board for looseness, corrosion, or breaks.

  3. 3

    Verify the drive's output phase currents are balanced (e.g., measure L1, L2, L3 output currents with an AC clamp meter) when a motor is connected.

  4. 4

    Perform an insulation resistance test on the motor windings and output cables to detect any phase-to-ground faults which could stress CTs.

  5. 5

    Confirm that motor rated current (P03-03) and motor nominal voltage (P03-02) parameters are accurately configured according to the motor nameplate.

Se alle koder i denne manualen (33)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: ABB ACS560 Standard Control Program Firmware