Oversetter...
7112
Brake Resistor Overheat
ABB · ACS800 Standard Firmware
Hva betyr 7112 ?
The brake resistor is overloaded, leading to excessive temperature. This can occur if the braking cycle is too demanding, if the supply AC voltage to the drive is excessive, or if the resistor overload protection is misconfigured, risking damage to the resistor.
Vanlige årsaker
- Braking resistor temperature sensor indicates overheat condition.
- Excessive regenerative energy from motor braking is overloading the resistor.
- Braking resistor is undersized for the application's duty cycle.
- Cooling fan for the braking resistor unit is not operating correctly.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Allow the brake resistor to cool down to a safe operating temperature.
- 2
Check parameter settings in parameter group 27 (BRAKE CHOPPER) related to resistor overload protection.
- 3
Verify that the braking cycle (duration, frequency, energy dissipation) meets the allowed operational limits for the installed resistor.
- 4
Measure the drive's AC supply voltage to ensure it is within specified limits and not excessively high.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: ABB ACS800 Standard Firmware