7302
Encoder Phase A/B Swapped
ABB · ACS800 Standard Firmware
Hva betyr 7302 ?
The pulse encoder phasing is incorrect, specifically Phase A is connected to the terminal for Phase B and vice versa. This will result in incorrect speed or position feedback, potentially causing motor rotation direction issues or control instability.
Vanlige årsaker
- Incorrect wiring of encoder phase signals A and B.
- Encoder signals A and B are reversed in the control unit configuration (P3-01, P3-02).
- Faulty encoder sensor generating swapped phase signals.
- Improper installation or setup of the encoder feedback.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Interchange the physical connections of pulse encoder phases A and B at the drive's encoder terminal block.
Verifisert teknisk data. Sist oppdatert: March 2026