Oversetter...
10020

Phase search failure

ABB · ACS850 Standard Program Firmware

Hva betyr 10020 ?

The required phase search process, essential for controlling 'encoder only' type motors, did not complete successfully. This indicates an issue with the motor's initial setup or feedback configuration. The motor cannot be properly controlled until this is resolved, potentially leading to incorrect or no motor movement.

Vanlige årsaker

  • Incorrect motor phase wiring (U, V, W) to drive output terminals (U, V, W) preventing accurate phase detection during search.
  • Encoder feedback issue (e.g., loose connection, faulty wiring, incorrect polarity) causing unreliable position signals during the search routine.
  • Motor not free to move or experiencing excessive mechanical load/friction during the phase search process.
  • Incorrect motor parameters (e.g., P0-01, P0-02, P0-03 for motor rated current, voltage, frequency) causing an unsuitable search profile.
  • Parameter P2-01 (Feedback device type) incorrectly set for an 'encoder only' motor requiring phase search.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify motor power cable connections at the drive output terminals (U, V, W) and motor terminal box are correct according to the motor's nameplate and drive manual.

  2. 2

    Check all encoder feedback cable connections at both the drive (e.g., X3, X4) and motor ends for secure seating and correct pin assignments.

  3. 3

    Ensure the motor shaft is free to rotate without external mechanical load or excessive friction during the phase search (e.g., disconnect mechanical coupling if possible).

  4. 4

    Review and confirm that motor parameters P0-01 (Rated current), P0-02 (Rated voltage), and P0-03 (Rated frequency) accurately match the motor's nameplate data.

  5. 5

    Attempt to re-run the phase search function from the drive's HMI or software (e.g., using a specific commissioning wizard or command).

  6. 6

    If the motor is equipped with an electric brake, ensure the brake is released or parameter P3-24 (Brake control) is configured correctly for the search operation.

Se alle koder i denne manualen (57)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: ABB ACS850 Standard Program Firmware