Rating ID mismatch
ABB · ACS880
Hva betyr 5093 ?
There is a discrepancy between the drive's physical hardware identification and the information stored in its memory unit. This often occurs after maintenance such as a firmware update or memory unit replacement, potentially preventing the drive from operating correctly or safely.
Vanlige årsaker
- Replacement of the control unit or memory module (e.g., EEPROM) without proper initialization or matching to the power unit.
- Firmware incompatibility between the power unit and control unit after an update or downgrade.
- Internal hardware fault on the control board or power unit leading to incorrect ID recognition.
- Corruption of the drive's non-volatile memory storing the rating ID.
- Incorrect power unit selected in drive configuration after a factory reset.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Perform a factory reset of the drive (e.g., parameter P9-01 = 1), then re-enter the power unit rating manually via parameter P0-01 (Drive Rating Code).
- 2
Verify the firmware versions of both the control unit and power unit are compatible (refer to drive manual).
- 3
If a control unit or memory module was recently replaced, ensure it is the correct part number for the power unit.
- 4
Re-upload parameters from a backup file after a factory reset.
- 5
Check for any physical damage or loose connections between the control board and the power unit sections of the drive.