7301

Motor speed feedback

ABB · ACS880

Hva betyr 7301 ?

No motor speed feedback signal is being received by the drive. This fault means the drive cannot accurately monitor motor speed, which is critical for closed-loop control and protection. The drive will likely trip or fail to start reliably, impacting performance and safety.

Vanlige årsaker

  • Encoder or resolver feedback cable damage (e.g., open circuit in signal lines, short to ground, poor shielding).
  • Encoder/resolver malfunction (e.g., internal failure, loss of 5VDC or 15VDC power supply to the device).
  • Incorrect wiring of feedback signals (e.g., A/B/Z signals swapped or connected to wrong terminals X20, X21).
  • Loose or corroded terminals at the encoder, motor junction box, or drive's feedback connector (e.g., X20, X21).
  • Excessive electromagnetic interference (EMI) on feedback cables without proper shielding and grounding.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify 5VDC or 15VDC power supply to the encoder at the encoder connector (e.g., pins 1 and 2).

  2. 2

    Check continuity of each signal wire (A, /A, B, /B, Z, /Z) from the encoder to the drive's feedback terminals (e.g., X20, X21).

  3. 3

    Visually inspect the encoder or resolver for mechanical damage, contamination, or loose mounting on the motor shaft.

  4. 4

    Confirm encoder parameters (e.g., P21-01 Encoder type, P21-02 Pulses per revolution) match the installed feedback device.

  5. 5

    Ensure proper shielding of the feedback cable is connected to ground at the drive's shield clamp and at the motor frame.

Se alle koder i denne manualen (116)