Oversetter...
FA82

Safe torque off 2

ABB · ACS880

Hva betyr FA82 ?

Safe Torque Off (STO) signal 2 has been lost or is not correctly applied. This fault often occurs in conjunction with 5091 (if running) or A5A0 (if stopped) and signifies a problem with the second leg of the dual-channel STO safety circuit. This compromise of the STO function prevents safe operation.

Vanlige årsaker

  • Open circuit or short circuit in the wiring for STO channel 2 (e.g., between safety relay output and XSTO2).
  • Failure of the external safety relay output supplying STO channel 2 (e.g., contact welding, coil failure).
  • Loss of the 24VDC supply to the external safety relay or the STO circuit itself.
  • Incorrect parameterization of STO supervision (e.g., parameter P50-01 STO supervision mode or delay).
  • Drive's internal monitoring circuit for STO2 detects an inconsistency (e.g., voltage out of tolerance).

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure the voltage at drive terminal XSTO2 relative to XSTO-COM; it should be 24VDC when STO is inactive.

  2. 2

    Check continuity of the wire connecting the external safety device output to drive terminal XSTO2.

  3. 3

    Verify the output status of the external safety relay or safety PLC responsible for STO channel 2.

  4. 4

    Confirm the 24VDC power supply to the external safety circuit is stable and within tolerance.

  5. 5

    Review parameter P50-01 (STO supervision mode) to ensure it is configured correctly for the application.

Se alle koder i denne manualen (116)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder