Suspend active
ABB · Application Error ABB Motion Drives Error trouble shoo
Hva betyr SUSPEND ACTIVE ?
The drive is in a 'Suspend active' state, indicating that the Mint SUSPEND command is active. This is not an error but a commanded state that prevents the firmware from loading and the drive from transitioning to normal operation.
Vanlige årsaker
- The Mint SUSPEND command has been activated, possibly unintentionally or as part of a debug routine.
- A previous program execution left the drive in a suspended state.
- Firmware loading is blocked due to an active suspension command.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Connect to the drive using Mint Workbench and check the status of any active SUSPEND commands.
- 2
Issue a RESUME command from Mint Workbench to clear the suspended state and allow firmware loading to proceed.
- 3
Review the Mint program code for any SUSPEND commands that might be inadvertently activated during boot or initialization.
- 4
Perform a factory reset if unable to clear the suspend state via software, understanding this will clear all parameters.