Oversetter...
FieldPowerOff
Field Power Off Condition
Allen-Bradley · Compact 5000 Digital I/O Modules
Hva betyr FieldPowerOff ?
This diagnostic indicates a field power off condition exists on the module or a specific test point. It signifies a loss of external power supplied to the module's I/O terminals, which powers the connected field devices. The tag automatically resets to 0 when the condition is removed.
Vanlige årsaker
- Loss of 24VDC field power supply to the module's I/O terminals
- Disconnected or damaged wiring for the field power supply
- Tripped circuit breaker or blown fuse in the field power supply circuit
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Measure the field power supply voltage at the module's designated field power terminals — expect 24VDC.
- 2
Check the status of the circuit breaker or fuse protecting the field power supply circuit.
- 3
Verify the integrity and connection of all field power wiring at the module and the power supply source.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: Allen-Bradley Compact 5000 Digital I/O Modules