Oversetter...
Ptxx.FieldPowerOff

Channel Field Power Loss

Allen-Bradley · Compact 5000 Digital I/O Modules

Hva betyr Ptxx.FieldPowerOff ?

This boolean tag indicates that a field power loss condition exists on the channel Ptxx. A tag value of '1' signifies that the external 24V DC field power supply for the channel is not present or has failed, disrupting channel operation.

Vanlige årsaker

  • Loss of the 24V DC field power supply connected to the module.
  • Blown fuse or tripped circuit breaker in the 24V DC field power supply circuit.
  • Improper or damaged wiring between the 24V DC field power supply and the module's field power terminals.
  • Failure of the 24V DC field power supply unit itself.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the 24V DC field power supply connected to the module is energized and producing the correct voltage (e.g., measure 24VDC at the module's field power input terminals).

  2. 2

    Check any fuses or reset any circuit breakers associated with the 24V DC field power supply circuit.

  3. 3

    Inspect the field power wiring connections to the module for integrity and secure termination.

Se alle koder i denne manualen (38)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Allen-Bradley Compact 5000 Digital I/O Modules