Chxx.FieldPowerOff

Channel Field Power Off (5069-IF8, 5069-OF4/K/8)

Allen-Bradley · Compact 5000 I/O Analog Modules

Hva betyr Chxx.FieldPowerOff ?

This boolean tag indicates that field power is not present at channel (xx). Field power is typically provided through the SA power connector on the controller, EtherNet/IP adapter, or field potential distributor. A value of 1 means field power is absent.

Vanlige årsaker

  • Field power is not supplied to the channel from the SA power connector
  • Issue with power supply from the controller, EtherNet/IP adapter, or field potential distributor

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify that field power (e.g., 24VDC) is present at the SA power connector of the controller, EtherNet/IP adapter, or field potential distributor.

  2. 2

    Check all connections providing field power to the module and channel (Chxx) terminals.

Se alle koder i denne manualen (33)