-1
Output Error
Allen-Bradley · MicroLogix 1400 Programmable Controllers
Hva betyr -1 ?
An invalid output has been specified for a PTOX instruction. Only Output 2, Output 3, and Output 4 are valid choices. This is a configuration error that causes the controller to fault, and the User Fault Routine does not execute.
Vanlige årsaker
- PTOX instruction configured to use an output other than the valid Output 2, Output 3, or Output 4.
- Typographical error or incorrect address assignment in the output parameter of the PTOX instruction.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify the PTOX instruction is configured to use a valid physical output (Output 2, Output 3, or Output 4).
- 2
Correct the output address specified in the PTOX instruction within the ladder program to one of the valid options.
Verifisert teknisk data. Sist oppdatert: March 2026