24
Decel Inhibit
Allen-Bradley · PowerFlex 700
Hva betyr 24 ?
The drive is not following a commanded deceleration because it is attempting to limit bus voltage. This indicates the DC bus voltage is rising due to regenerative energy, potentially exceeding safe limits and causing the drive to inhibit deceleration.
Vanlige årsaker
- External signal preventing deceleration (e.g., motor brake active).
- Internal logic error during deceleration command.
- Deceleration ramp time set too short for the load.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify input voltage is within the drive's specified limits.
- 2
Verify system ground impedance follows proper grounding techniques.
- 3
Disable bus regulation and/or add a dynamic brake resistor and/or extend the deceleration time parameter.
Verifisert teknisk data. Sist oppdatert: March 2026