DPI Port Communication Loss
Allen-Bradley · PowerFlex 700
Hva betyr 81-85 ?
A DPI port has stopped communicating, or a SCANport device was connected to a drive operating DPI devices at 500k baud. This indicates a loss of communication with a connected DPI device, which can prevent control commands or feedback from reaching the drive. The fault code varies depending on which port (1-5) lost communication.
Vanlige årsaker
- Loss of communication on the DPI (Drive Parallel Interface) port.
- Faulty DPI cable connection.
- Incorrect DPI addressing or configuration (e.g., P8-xx parameters).
- Communication failure with the connected device on the DPI bus.
- DPI device not powered or malfunctioning.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
If the adapter was not intentionally disconnected, check the wiring to the affected DPI port.
- 2
Check the HIM (Human Interface Module) connection.
- 3
If an adapter was intentionally disconnected and the [Logic Mask] bit for that adapter is set to "1", set the [Logic Mask] bit for the adapter to "0" to disable this fault.
- 4
Replace wiring, port expander, adapters, or Main Control Board as required.