Encoder Quadrature Error
Allen-Bradley · PowerFlex 700
Hva betyr 90 ?
Both encoder channels (A and B) changed state within a single clock cycle. This suggests an issue with the encoder signal quality, possibly due to electrical noise or a damaged encoder, causing incorrect speed or position feedback.
Vanlige årsaker
- Encoder signals A and B are reversed or swapped.
- Encoder pulses are inconsistent or noisy.
- Incorrect encoder resolution set in drive parameters (e.g., P4-01).
- Faulty encoder or internal logic issue.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check for externally induced noise on encoder cabling (e.g., proximity to power cables, proper shielding and grounding).
- 2
Replace the encoder unit.