Oversetter...
Diag3:off, Diag4:2_pulses

Communication Error

Beckhoff · EL6900 Operating Instructions

Hva betyr Diag3:off, Diag4:2_pulses ?

This diagnostic flashing code (Diag 3 off, Diag 4: 2 flash pulses with longer pause) indicates a communication error within one of the TwinSAFE groups. This suggests issues with data exchange between safety devices on the EtherCAT network, potentially due to faulty wiring, incorrect addressing, or timing discrepancies.

Vanlige årsaker

  • A communication failure has been detected between the device and its master or other connected devices.
  • Loss of signal or data integrity on the communication bus.
  • Timeout on expected communication messages from a peer device.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the EtherCAT communication status of all TwinSAFE slaves connected to the EL6900 in the TwinCAT System Manager, checking for lost frames or slave state changes.

  2. 2

    Inspect the EtherCAT cables and connectors for damage, proper seating, and correct shielding between the EL6900 and connected TwinSAFE slaves.

  3. 3

    Check the EtherCAT network topology and addressing configuration in TwinCAT to ensure it precisely matches the safety project setup.

Se alle koder i denne manualen (16)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Beckhoff EL6900 Operating Instructions