Invalid Argument Provided
Beckhoff · TwinCAT 2 Automation Interface
Hva betyr E_INVALIDARG ?
An invalid argument was supplied to the function. For OpenConfiguration(), the bstrFile path does not refer to a valid TwinCAT configuration file. For SaveConfiguration(), the bstrFile path is invalid for saving. For LinkVariables(), the offs1, offs2, or size parameters do not match the variables' structure or range.
Vanlige årsaker
- A parameter value is outside its defined acceptable range (e.g., P1-54 > 100).
- An incorrect data type was provided for a configuration setting.
- A command was issued with missing or malformed arguments.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
For OpenConfiguration() and SaveConfiguration(): Verify the bstrFile parameter points to an existing, valid .wsm configuration file or a valid, writable output path, respectively.
- 2
For LinkVariables(): Inspect offs1, offs2, and size values to ensure they are within the logical bounds and bit/byte alignment of the target variables.
- 3
Check for any illegal characters, incorrect syntax, or inaccessible locations in file paths or parameter values.