E2061

Device overload prewarning

Bosch Rexroth · IndraDrive C Drive Controllers

Hva betyr E2061 ?

The drive controller or associated power electronics are experiencing an elevated load, approaching their thermal capacity. Continued operation at this level could lead to a device shutdown.

Vanlige årsaker

  • Continuous operation at or above the drive's rated current.
  • Motor operating under excessive mechanical load.
  • Inadequate cooling for the drive controller, possibly due to blocked vents, fan failure, or high ambient temperature.
  • Incorrect drive parameters (e.g., motor data) causing the drive to misinterpret its internal load.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the mechanical load on the motor and ensure it is within the drive's continuous operating current limits.

  2. 2

    Check the drive's cooling fan for proper operation and ensure ventilation openings are clear of obstructions.

  3. 3

    Measure the ambient temperature around the drive and ensure it is within the specified operating range.

  4. 4

    Review drive parameters for motor current, load limits, and thermal model settings to ensure they are configured correctly.