F2819

Mains failure

Bosch Rexroth · IndraDrive MPx02

Hva betyr F2819 ?

A complete loss of the AC mains input power supply has occurred. The drive is no longer receiving power from the grid, which means it cannot operate and will initiate a controlled shutdown. This fault indicates that the entire power source is interrupted, not just a single phase.

Vanlige årsaker

  • Main circuit breaker tripped or opened
  • Complete power outage on the supply line
  • Emergency stop activated, cutting main power
  • Loose or disconnected main power supply cable
  • External fault device (e.g., ground fault interrupter) tripped

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the status of the main circuit breaker, fuses, or upstream contactor that supplies power to the drive and confirm it is closed/active.

  2. 2

    Measure the incoming AC mains voltage directly at the drive's input terminals (L1, L2, L3) and confirm it matches the nominal supply voltage specified for the drive.

  3. 3

    Inspect all incoming power cables, terminal blocks, and connections from the main power source up to the drive's input terminals for any signs of damage, loose connections, or disconnections.

  4. 4

    Check for any plant-wide power outages, local emergency power-off activations, or tripped main distribution board breakers that could affect the entire system or power branch supplying the drive.