Oversetter...
833
%s-axis for switchover in SERCOS phase 3 not ready (covers 833-834, 836).
Bosch Rexroth · Motion Control
Hva betyr 833 ?
The specified axis ('%s') is not ready for switchover to SERCOS phase 3, due to missing or incorrect identification number S-0-0021. This fault (covering codes 833-834 and 836) indicates the drive rejects the phase change because of parameter validation issues. It is a servo loop or drive fault.
Vanlige årsaker
- Drive rejection of SERCOS phase 3 switching due to missing ident number S-0-0021.
- Drive rejection of SERCOS phase 3 switching due to incorrect ident number S-0-0021.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Read out ident number S-0-0021 of the affected axis.
- 2
Correct any missing or wrong value for ident number S-0-0021.
- 3
Initiate a new SERCOS startup after correcting the ident number.
Verifisert teknisk data. Sist oppdatert: March 2026
Relaterte feilkoder
Kilde: Bosch Rexroth Motion Control