Oversetter...
1

10 Volts low

Danfoss · VLT AutomationDrive FC 301/302

Hva betyr 1 ?

The control card voltage on terminal 50 is less than 10 V, indicating an overload on the 10 V supply. This can be caused by a short circuit in a connected potentiometer or incorrect wiring of the potentiometer.

Vanlige årsaker

  • Short circuit in a connected potentiometer (e.g., between terminal 50 and terminal 53).
  • External device connected to the 10V supply (terminal 50) is drawing excessive current, causing an overload.
  • Damaged or degraded potentiometer connected to terminal 50, creating a resistive short or low impedance path.
  • Multiple external devices drawing current from the 10V supply (terminal 50) exceeding the drive's specified current limit.
  • Internal control card component failure (e.g., voltage regulator U101) responsible for the 10V output.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Disconnect all external wiring from terminal 50 (10V supply) and terminal 53 (0V supply) on the control card.

  2. 2

    Measure the voltage between terminal 50 and terminal 53 on the control card; it should read approximately 10VDC.

  3. 3

    If the voltage is correct, reconnect external devices one by one, monitoring the voltage between terminal 50 and 53 after each connection.

  4. 4

    If a potentiometer is connected, measure its resistance across the end terminals (e.g., 50-53) and its wiper (e.g., 50-54) for shorts.

  5. 5

    Check the total current draw from the 10V supply (terminal 50) when all external devices are connected, ensuring it's below the drive's specified limit (e.g., 100mA).

Se alle koder i denne manualen (66)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Danfoss VLT AutomationDrive FC 301/302