Short circuit
Danfoss · VLT AutomationDrive FC 301/302
Hva betyr 16 ?
A short-circuit condition is detected either in the motor windings or within the motor wiring connecting to the frequency converter. This poses a significant risk of damage to the drive and motor if not resolved.
Vanlige årsaker
- Phase-to-phase short-circuit within the motor windings.
- Short-circuit between two or more motor output phases in the motor cable (e.g., U-V, V-W, U-W).
- Mechanical damage to the motor cable causing direct contact between phase conductors.
- Water ingress or severe contamination in the motor terminal box creating a conductive path between phases.
- Internal fault within the drive's output stage (e.g., failed IGBT module, gate drive circuit failure).
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Power down the drive and disconnect the motor leads (U, V, W) from the drive's output terminals.
- 2
Use a multimeter to measure the resistance between each pair of motor phases (U-V, V-W, W-U) for both the motor cable and motor windings. Look for resistance values close to zero Ohms.
- 3
Inspect the entire length of the motor cable for severe physical damage, crushing, or cuts that could cause phase-to-phase contact.
- 4
Open the motor terminal box and inspect for moisture, carbon tracking, or debris bridging terminals.
- 5
If the motor and cable show no short-circuit, the fault likely lies within the drive's power section (e.g., IGBT module), requiring service.