Oversetter...
26

Brake resistor power limit

Danfoss · VLT AutomationDrive FC 301/302

Hva betyr 26 ?

The power transmitted to the brake resistor, calculated as an average over the last 120 seconds, exceeds 90% of its capacity. If option [2] Trip is selected in parameter 2-13 Brake Power Monitoring, the frequency converter trips when dissipated braking power reaches 100%.

Vanlige årsaker

  • Frequent or prolonged regenerative braking operations exceeding the brake resistor's average power rating.
  • Brake resistor is undersized for the application's regenerative energy requirements (e.g., too low a continuous power rating).
  • Deceleration ramp times (P3-42) set too aggressively, generating high peak regenerative power that averages to exceed capacity.
  • Faulty brake chopper control causing it to dissipate energy inefficiently or excessively.
  • Parameter P2-13 (Brake Power Monitoring) set to [2] Trip, causing a trip rather than just a warning.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Monitor the actual brake resistor power dissipation (e.g., via LCP if available) during regenerative operations.

  2. 2

    Increase the deceleration ramp time (P3-42 Decel Ramp Time) to spread regenerative energy over a longer period.

  3. 3

    Verify the brake resistor's specified continuous power rating and compare it to the application's maximum regenerative power.

  4. 4

    Consider upsizing the brake resistor to one with a higher continuous power rating (e.g., from 1kW to 2kW).

  5. 5

    Change parameter P2-13 (Brake Power Monitoring) to option [1] Warning to allow continued operation with a warning state.

  6. 6

    Check the drive's load profile and cycle time to determine if the application inherently requires a larger resistor.

Se alle koder i denne manualen (66)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Danfoss VLT AutomationDrive FC 301/302