Oversetter...
ALARM 32

Motor phase W missing

Danfoss · VLT HVAC Basic FC 101

Hva betyr ALARM 32 ?

The motor phase W connection between the frequency converter and the motor is missing or interrupted. This prevents proper motor operation and can lead to damage if ignored.

Vanlige årsaker

  • Loose or disconnected conductor at the drive output terminal W.
  • Loose or disconnected conductor at the motor terminal W.
  • Break or high resistance in the motor cable's W phase conductor.
  • Faulty contactor or circuit breaker in the motor output circuit (if present) for phase W.
  • Failure of the drive's output power stage (e.g., IGBT) specifically for phase W.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Power off the drive and disconnect input power. Visually inspect and tighten connections for the W-phase motor cable at both the drive's W output terminal and the motor's W terminal.

  2. 2

    Measure the resistance of the W-phase motor cable conductor from the drive end to the motor end to check for continuity (expect < 1 Ohm).

  3. 3

    With motor cables disconnected from the drive, measure the resistance between motor terminals W-U, W-V, and U-V. All three values should be balanced and low.

  4. 4

    Check for any external fusing or contactors in the W-phase motor circuit for continuity and proper operation.

  5. 5

    If cable and motor are verified good, the fault indicates a potential internal drive hardware issue with the W-phase output.

Se alle koder i denne manualen (40)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Danfoss VLT HVAC Basic FC 101