Oversetter...
ALARM 69

Power card temperature

Danfoss · VLT HVAC Basic FC 101

Hva betyr ALARM 69 ?

The temperature on the frequency converter's power card is outside its acceptable operating range (either too high or too low). Extreme temperatures can lead to premature component failure or immediate drive shutdown to prevent damage.

Vanlige årsaker

  • Blocked cooling air vents or heatsinks, preventing proper heat dissipation from the power card.
  • Failed cooling fan (e.g., seized, not rotating, low RPM) within the frequency converter.
  • Excessive ambient temperature in the control cabinet or operating environment, exceeding drive limits.
  • Drive cabinet ventilation fan failure or insufficient cooling, resulting in heat accumulation.
  • Sustained operation at high loads or with highly dynamic cycles without sufficient cooling.
  • Internal power card temperature sensor fault or drift.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the drive's cooling fan operation; verify it spins freely and replace if seized or noisy.

  2. 2

    Inspect all cooling air vents and heatsinks for dust, debris, or blockages, and clean them thoroughly.

  3. 3

    Measure the ambient air temperature inside the control cabinet and around the drive; ensure it is within specified limits.

  4. 4

    Verify motor nominal current (P1-21) and motor nominal power (P1-22) are correctly set, and AMA has been performed.

  5. 5

    Ensure the drive is not undersized for the application, leading to continuous high current draw.

  6. 6

    For low temperature, consider adding cabinet heating or temporary shielding for cold startup.

Se alle koder i denne manualen (40)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Danfoss VLT HVAC Basic FC 101