Option module configuration has changed
Danfoss · VLT HVAC Drive FC 102
Hva betyr 67 ?
One or more option modules (e.g., fieldbus cards, I/O extensions) have either been added or removed since the last power-down cycle. The drive detects a change in its hardware configuration and requires user confirmation. This alarm serves as a notification and requires a reset to ensure the change was intentional before proceeding.
Vanlige årsaker
- An option module (e.g., Profibus card, I/O module) has been physically added or removed since the last power cycle.
- An existing option module is not properly seated in its slot on the control card, causing intermittent detection.
- A newly installed or re-seated option module requires explicit acknowledgement or initialization through parameter P14-22 (Auto Configuration).
- Faulty option module causing inconsistent identification by the main control board.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
1. Power down the drive, then visually inspect and re-seat all installed option modules firmly into their respective slots.
- 2
2. Verify the drive's parameter P14-22 (Auto Configuration) is set to '1' (Enable) to detect module changes.
- 3
3. If an option module was recently added or removed, confirm its presence or absence matches the intended configuration.
- 4
4. Power cycle the frequency converter and observe if the fault reoccurs; if so, test with a known good option module.