Oversetter...
257

Internal fault (Power EEPROM data defective or too old)

Danfoss · VLT HVAC Drive High Power

Hva betyr 257 ?

The power EEPROM data is defective or too old. This indicates a corruption or obsolescence of the non-volatile memory storing power section parameters.

Vanlige årsaker

  • Corruption of data stored in the power section's EEPROM (Electrically Erasable Programmable Read-Only Memory) due to noise or power fluctuation.
  • Degradation or wear-out of the EEPROM memory cells over time due to exceeding specified write/erase cycles.
  • Incompatibility between a new firmware version and the existing data format in the power EEPROM.
  • Internal communication error between the main CPU and the power EEPROM chip, leading to data access issues.
  • Manufacturing defect in the EEPROM chip itself or its associated circuitry on the power board.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    1. Back up all parameters from the frequency converter (if accessible via control panel or software).

  2. 2

    2. Perform a factory reset (e.g., Parameter P14-22 Load defaults) to clear corrupted EEPROM data.

  3. 3

    3. Download the backed-up parameters to the frequency converter after the factory reset.

  4. 4

    4. Power cycle the frequency converter (main input power off for 5 minutes) and observe if the fault clears.

  5. 5

    5. Verify the frequency converter's firmware version is up-to-date and compatible with any recent changes or system updates.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Danfoss VLT HVAC Drive High Power