Oversetter...
ALARM 14

Earth (ground) fault

Danfoss · VLT HVAC Drive High Power

Hva betyr ALARM 14 ?

Current is flowing from the output phases to ground, either in the cable between the frequency converter and the motor, or within the motor itself. This is a severe fault that can cause electrocution, fire, and damage to the frequency converter or motor.

Vanlige årsaker

  • Insulation breakdown in the motor windings, causing a path for current to flow to the motor frame (ground).
  • Damaged or improperly installed motor cable (e.g., crushed, cut, water ingress) leading to insulation failure to ground.
  • Water or contamination ingress into the motor terminal box or frequency converter output terminals (U, V, W).
  • Incorrectly terminated motor cable shields, or shield damage, allowing phase-to-ground contact.
  • Faulty ground detection circuit within the frequency converter.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Disconnect the motor cables (U, V, W) from the frequency converter output terminals and measure insulation resistance from each motor phase to ground using a megohmmeter (e.g., 500VDC).

  2. 2

    Perform a visual inspection of the motor cable for any signs of damage, crushing, or water ingress along its entire length.

  3. 3

    Check the motor terminal box for any signs of moisture, contamination, or loose wiring that could cause a ground fault.

  4. 4

    Verify proper grounding of both the motor frame and the frequency converter chassis to the plant's earth ground system.

  5. 5

    Isolate the fault by first testing the motor cable separately (disconnected from motor and frequency converter) for insulation resistance to ground.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Danfoss VLT HVAC Drive High Power