410

Servo Position Error (Stop State)

Fanuc · Alpha i series AC Servo Motor

Hva betyr 410 ?

The servo position error in the stopped state is larger than the value specified in parameter No.110. This indicates that the motor is not holding its commanded position accurately while stationary, possibly due to mechanical backlash or insufficient holding torque.

Vanlige årsaker

  • Mechanical cause of large position error, such as backlash, loose coupling, or external force.
  • Parameter No.110 (position error limit in stop state) is set too low for the application.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Inspect the mechanical system for any sources of position error (e.g., backlash, loose components, external forces).

  2. 2

    If no mechanical cause is found, increase the value of parameter No.110 to a suitable limit.