Abnormal Charge of Capacitor Module (ECM)
Fanuc · Macro B CNC Programming
Hva betyr E ?
The Energy Charge Module's (ECM) Capacitor Modules are not charging normally. This indicates a failure in the charging process, possibly due to a fault in the Capacitor Module itself (A06B-6158-H020), the charging control circuit, or insufficient power supply.
Vanlige årsaker
- Abnormal charging behavior of the capacitor module (ECM).
- Faulty charging circuit within the ECM.
- Capacitor module (ECM) leakage current exceeds acceptable levels.
- External influences causing erratic charging profiles.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Immediately stop the machine using the emergency stop button and open the external Main Circuit Contactor (MCC) of the Power supply.
- 2
Inspect the Capacitor Modules (A06B-6158-H020) for any visible damage or signs of malfunction, such as bulging or leakage.
- 3
Check the connections between the ECM Control Module (A06B-6158-H010) and the Capacitor Modules for secure contact and continuity.
- 4
Verify the functionality of the DC Reactor (A06B-6158-H040), which smooths the charge and discharge current (page 578).
- 5
Measure the input power to the ECM to ensure it meets the requirements for charging the capacitor modules.