Oversetter...
SRVO-105

Door Open or Emergency Stop

Fanuc · R-30iB Mate + Mate Plus Robot

Hva betyr SRVO-105 ?

This alarm indicates that the cabinet door is open or an emergency stop condition is active, triggering a safety interlock. This prevents robot operation until the safety condition is resolved, ensuring operator and equipment safety.

Vanlige årsaker

  • External emergency stop button activated.
  • Safety interlock switch for a door is open.
  • Internal safety circuit fault in the control panel.
  • Configuration error for safety inputs (e.g., P5-01).

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    If an auxiliary cabinet (option) is installed, check whether its door is open and ensure it is securely closed.

  2. 2

    If an auxiliary cabinet is installed, check the door switch and its wiring for faults; replace if necessary.

  3. 3

    Check that the CRMA92 and CRMB8 connectors on the E-STOP unit and the CRMA91 connector on the 6-Axis servo amplifier are connected securely.

  4. 4

    Replace the emergency stop board.

  5. 5

    Replace the 6-Axis servo amplifier.

Se alle koder i denne manualen (53)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Fanuc R-30iB Mate + Mate Plus Robot