Safety Chain 2 Abnormal
Fanuc · R-30iB Mate + Mate Plus Robot
Hva betyr SRVO-231 ?
A mismatch has occurred between duplicate safety signals. Specifically, a contact on the chain 1 side (e.g., between EES1 and EES11, or EAS1 and EAS11) is open, while the corresponding contact on the chain 2 side (e.g., between EES2 and EES21, or EAS2 and EAS21) is closed. This condition indicates a potential failure or discrepancy in one of the redundant safety circuits, compromising safety integrity.
Vanlige årsaker
- Safety Chain 2 has detected an abnormal condition, interrupting normal operation.
- Similar to Safety Chain 1, this fault is related to the second safety interlock circuit, indicating an issue with its components or wiring.
- The control system has halted operation due to a fault in the secondary safety monitoring system.
- Inspect all components and wiring connected to Safety Chain 2 for faults.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check any other SRVO-266 through SRVO-275 and SRVO-370 through SRVO-385 alarms issued simultaneously to identify the specific signal with the mismatch.
- 2
Take corrective action(s) as described for any concurrently issued alarms.
- 3
Do not reset the chain error alarm until the failure is identified and repaired to ensure safety.
- 4
After correcting the cause of the alarm, perform the chain error reset procedure as described in the manual.