Oversetter...
366

PULSE MISS(INT)

Fanuc · Series 0i-D/0i Mate-D Maintenance

Hva betyr 366 ?

This alarm on Fanuc Series 0i-D/0i Mate-D with αi/βi Pulsecoders indicates a small internal signal amplitude from the built-in Pulsecoder. This can be caused by the Pulsecoder itself failing or by external electrical noise affecting the signal integrity.

Vanlige årsaker

  • Internal failure of the Pulsecoder causing weak signal output.
  • Electrical noise interfering with the Pulsecoder signal lines.
  • Damaged or degraded Pulsecoder cable reducing signal amplitude.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Inspect the Pulsecoder cable for any damage, proper shielding, and secure connections at both the Pulsecoder and the servo amplifier.

  2. 2

    Check for and eliminate potential sources of electrical noise (e.g., power cables, induction) in the vicinity of the Pulsecoder and its cabling.

  3. 3

    Verify the supply voltage to the Pulsecoder, ensuring it is within specified limits as per the wiring diagram.

  4. 4

    If cabling, noise, and supply voltage are confirmed to be correct, replace the Pulsecoder unit.

Se alle koder i denne manualen (60)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Fanuc Series 0i-D/0i Mate-D Maintenance