Inverter Control Power Supply Undervoltage (SVM)

Fanuc · Series 30i CNC

Hva betyr 2 ?

This alarm indicates an undervoltage condition in the control power supply of the Servo Amplifier Module (SVM). The control power supply (typically 24VDC) is essential for the internal logic and control circuitry of the inverter. A voltage drop below 22.8V can cause erratic behavior or module shutdown.

Vanlige årsaker

  • Three-phase input voltage of the amplifier has dropped below 85% of its rated input voltage.
  • The 24 V power supply voltage output from the PSM is lower than 22.8 V.
  • Issues with the connector or cable (CXA2A/B) supplying control power.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the three-phase input voltage of the amplifier — verify it is not lower than 85% of the rated input voltage.

  2. 2

    Check the 24 V power supply voltage output from the PSM — verify it is not lower than 22.8 V.

  3. 3

    Inspect the connector and cable (CXA2A/B) for damage, loose connections, or incorrect seating.

  4. 4

    Replace the SVM if all power supply and cable checks are normal but the alarm persists.