Electrolyte Circulation Defective
Fronius · Perfect Charging
Hva betyr 14 ?
This fault indicates that the electrolyte circulation system is not functioning correctly, specifically that the pressure switch is not activating. This condition is critical for certain battery types requiring active electrolyte management to prevent issues like overheating or stratification during charging.
Vanlige årsaker
- A faulty pressure switch in the electrolyte circulation system that fails to detect flow or pressure.
- Blockage within the electrolyte circulation lines or a malfunction of the electrolyte pump.
- Insufficient electrolyte level in the battery cells, preventing adequate circulation.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify the operation of the pressure switch by checking its electrical state when circulation should be active.
- 2
Inspect the electrolyte circulation pump for any blockages, debris, or signs of operational failure.
- 3
Check the electrolyte level in all battery cells and replenish if it is below the manufacturer's recommended level.
Verifisert teknisk data. Sist oppdatert: March 2026