Oversetter...
1083

Insulation Fault Warning

Fronius · Symo Advanced

Hva betyr 1083 ?

Status code 1083 is displayed when the measured insulation resistance drops below a predefined threshold, indicating a potential insulation fault in the system. This warning is output when the 'Insulation warning' parameter is activated. The system's 'Insulation measurement mode' determines the accuracy and display of this value.

Vanlige årsaker

  • Insulation resistance dropping below the set 'Threshold for the insulation warning'.
  • An insulation fault within the PV system or associated wiring.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Verify the 'Insulation warning' parameter is set to 'On' to enable insulation monitoring.

  2. 2

    Check the 'Threshold for the insulation warning' parameter value (100000 - 10000000 Ω) and adjust if appropriate for the installation.

  3. 3

    If 'Insulation measurement mode' is set to 'Fast', change it to 'Exact' to display the measured insulation resistance on the user interface and get a more accurate reading.

  4. 4

    Perform an insulation resistance test on the PV array and wiring to identify the specific location of the fault.

Se alle koder i denne manualen (41)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder