Oversetter...
108

String 3 Abnormal

Huawei · SUN2000 8-28KTL Solar Inverter

Hva betyr 108 ?

A warning indicating that PV string 3 is performing abnormally, possibly due to long-term shielding or deterioration. This results in reduced power output from the specific string, decreasing overall system efficiency.

Vanlige årsaker

  • PV string 3 has been shielded for a long time.
  • PV string 3 has deteriorated.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check whether the output current of PV string 3 is significantly less than the output current of other PV strings.

  2. 2

    If current is low, check whether PV string 3 is shielded by contaminants or obstructions.

  3. 3

    If PV string 3 is clean and not shielded, check individual PV modules within string 3 for faults.

Se alle koder i denne manualen (26)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder

Kilde: Huawei SUN2000 8-28KTL Solar Inverter