318

Residual Current Abnormal

Huawei · SUN2000 8-28KTL Solar Inverter

Hva betyr 318 ?

A major fault indicating that the insulation resistance against ground on the input side of the SUN2000 has decreased during operation, leading to an excessively high residual current. This implies a potential ground fault or insulation breakdown, causing inverter shutdown.

Vanlige årsaker

  • An accidental external circuit abnormality.
  • The insulation resistance against ground of PV strings is too low.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Observe if the SUN2000 automatically reverts to normal operating status if the alarm occurred accidentally due to a temporary external circuit abnormality.

  2. 2

    If the alarm occurs repeatedly or persists for a long time, check whether the insulation resistance against ground of PV strings is too low.