F219

Motor Overtemperature Shutdown

Indramat · ECODRIVE Controller

Hva betyr F219 ?

The motor temperature has risen to an unacceptable level. As soon as the temperature error threshold (155°C) is exceeded, the drive will immediately bring the motor to a standstill as set in parameter P-0-0119 (best possible standstill).

Vanlige årsaker

  • The motor was overloaded; the effective torque demanded was above its allowable continuous torque level for too long.
  • Break in line, ground short, or short circuit in the motor temperature monitor line.
  • Instability in the velocity loop.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the installation and loading of the motor. Verify if operating conditions have changed (e.g., pollution, friction, moved components).

  2. 2

    Check wires and cables to the motor temperature monitor for wire breaks, earth short circuits, or short circuits.

  3. 3

    Review and adjust the velocity loop parameters in the ECODRIVE DKC01.1/DKC11.1 controller for stability.