F870

+24 V Error

Indramat · ECODRIVE Controller

Hva betyr F870 ?

The ECODRIVE DKC01.1/DKC11.1 drive requires a 24V control voltage. If this voltage deviates more than +/- 20% from 24V, the drive immediately switches to torque-free operation, activates an optional brake, and switches off encoder emulation.

Vanlige årsaker

  • Disturbance or overload of the 24V supply voltage.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure the 24V control voltage supplied to the ECODRIVE DKC01.1/DKC11.1 drive and verify it is within the allowed +/- 20% tolerance.

  2. 2

    Check all wiring connections for the 24V supply for loose terminals, damage, or intermittent contact.

  3. 3

    Identify and isolate any external devices connected to the 24V supply that might be drawing excessive current or causing disturbances.

  4. 4

    If wiring and external load are normal, replace the power supply module (either internal or external, depending on the system design).

  5. 5

    Clear the error in parametrization mode (phase 2) after resolving the underlying issue.