Target position out of travel range
Indramat · IndraDrive MPx02
Hva betyr E2053 ?
The commanded target position for the IndraDrive MPx02 is outside the defined mechanical or software travel limits of the axis. This warning prevents the drive from moving the axis to a potentially damaging or undesired physical location, ensuring machine safety and integrity.
Vanlige årsaker
- The target position from the master controller exceeds the configured positive or negative software limit switches (e.g., P-0-0045, Position limit positive; P-0-0046, Position limit negative).
- Mechanical hard stops are set within the software limits, or the software limits are too restrictive for the application's operational range.
- Loss of position reference or incorrect homing offset, causing the drive to misinterpret the current position relative to limits.
- Incorrect scaling of position units between the master controller and the drive.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify the commanded target position from the master control system (PLC/CNC) and ensure it falls within the defined operational travel range.
- 2
Check the drive's software travel limit parameters, such as P-0-0045 (Position limit positive) and P-0-0046 (Position limit negative), and adjust them if they are too restrictive or incorrectly set.
- 3
Inspect the mechanical system for any physical hard stops or limit switches that might be activated prematurely or define a smaller range than intended.
- 4
Review the homing procedure and absolute position reference to ensure the drive's coordinate system is correctly aligned with the mechanical system.
- 5
If necessary, manually jog the axis to a valid position within the defined travel limits.