Positive position limit exceeded
Indramat · IndraDrive MPx02
Hva betyr E8029 ?
The IndraDrive MPx02 has detected that the actual position of the axis has moved beyond the configured positive software travel limit (P-0-0045). This warning indicates that the axis has entered a restricted zone, and further movement in the positive direction may be prevented or cause a fault, protecting the machine from overtravel.
Vanlige årsaker
- Actual axis position exceeded the programmed P-0-0045 limit due to an aggressive motion command or external force.
- Incorrect setting of the positive software travel limit (P-0-0045) relative to the physical machine limits.
- Loss of position reference or incorrect homing offset, causing the drive to misinterpret its current position.
- Mechanical overtravel due to momentum or external force exceeding the drive's ability to stop within limits.
- Errors in position scaling or unit conversion.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Check the actual position of the axis and compare it to the configured positive software travel limit P-0-0045.
- 2
Move the axis manually or with a small negative jog command to bring it back within the permissible travel range.
- 3
Verify and adjust the parameter P-0-0045 (Position limit positive) to correctly match the physical positive travel limit of the machine, ensuring it provides adequate mechanical clearance.
- 4
Perform a homing procedure to re-establish the correct position reference if it may have been lost or corrupted.
- 5
Review the motion commands from the master controller to ensure target positions do not exceed the defined limits.