Invalid control section/firmware combination
Indramat · Indradrive
Hva betyr F8120 ?
The firmware loaded on the IndraDrive is not compatible with the detected control section hardware. This mismatch prevents the control unit from operating correctly, potentially due to incorrect firmware installation or a control section replacement with an incompatible model.
Vanlige årsaker
- Firmware update was performed with an incorrect version for the specific control section.
- Control section module was replaced with one that is incompatible with the existing firmware.
- Corruption of firmware or hardware identification data within the control unit.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Verify the part numbers and versions of the IndraDrive control section and the installed firmware.
- 2
Ensure that the firmware version is specifically designed and certified for the exact control section model installed.
- 3
If an incompatible firmware was installed, download and flash the correct firmware version.
- 4
If the control section was replaced, ensure it is compatible with the drive's power section and existing firmware.
- 5
Consult the IndraDrive documentation for compatible firmware and hardware combinations.