CONTACTOR CLOSED
Kone · Elevator Control
Hva betyr 1037 ?
The motor controller (codes 1037, 2037, 3037) has detected that the main contactor is closed when it should be open. This indicates a contactor control issue or a welded contact. The specific lift reaction is controller dependent.
Vanlige årsaker
- Contactor welded closed due to overcurrent or age.
- Contactor feedback circuit fault, indicating a false closed status.
- Contactor control signal error, inadvertently keeping the contactor closed.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Measure voltage across the main contactor coil terminals to confirm it is de-energized when the controller commands an open state.
- 2
Inspect the main contactor for physical signs of mechanical damage, binding, or evidence of contact welding/overheating.
- 3
Perform a continuity test on the main power contacts of the contactor with the coil de-energized to verify they are open.
- 4
Verify the controller's digital output signal for the main contactor coil transitions to the correct state (e.g., 0V/OFF) at the controller's terminal block when commanded open.