0125

Torque limit exceeded

Kone · V3F25/18 drive

Hva betyr 0125 ?

The MXTORQ (6_9) parameter shows '-', '--', or an emergency stop occurs during acceleration on the V3F25/18 drive. This indicates that the motor torque has exceeded the configured maximum limit.

Vanlige årsaker

  • Incorrect parameter settings for MXTORQ (6_9).
  • Issues with the motor cable connections.
  • The value of the Torque scaling (6_40) parameter is set too low.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check the parameters for MXTORQ (6_9).

  2. 2

    Check the motor cable connections for integrity.

  3. 3

    Increase the value of the Torque scaling (6_40) parameter.