Oversetter...
131

OV1-Trip (Overvoltage in intermediate circuit while charging)

Kuka · KR C2 Robot Controller

Hva betyr 131 ?

This fault indicates an overvoltage condition in the intermediate DC bus circuit during the charging phase (KPS-600). This can be caused by excessive input voltage or issues with the charging circuit, risking damage to power components if the voltage exceeds safe limits.

Vanlige årsaker

  • OV1-Trip: Overvoltage detected in the intermediate circuit during charging (P1-15).
  • Regenerative braking not effectively dissipating energy.
  • External power source providing excessive voltage.
  • Defect in the drive's DC bus smoothing capacitors.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Measure the incoming AC line voltage (L1-L2, L2-L3, L3-L1) at the drive input terminals — ensure it is within the drive's specified input range.

  2. 2

    Measure the DC bus voltage at terminals +UDC/-UDC during the charging sequence.

  3. 3

    Verify the external power supply quality for voltage stability and absence of spikes.

Se alle koder i denne manualen (58)
Verifisert teknisk data. Sist oppdatert: March 2026

Relaterte feilkoder