Undervoltage PMx
KPS Low-Voltage Supply Undervoltage
Kuka · KR C2 Robot Controller
Hva betyr Undervoltage PMx ?
The low-voltage supply for the KPS module (PMx) is experiencing an undervoltage condition. The rated voltage for this supply is 27.1 V.
Vanlige årsaker
- Main supply voltage to the KPS drive is too low.
- Insufficient input power from the grid or transformer.
- Issue with the power supply wiring or connections.
- Internal voltage regulation fault within the drive.
Reparasjonssteg & Sjekkliste
Klikk på steg for å spore fremgangen.
- 1
Measure the low-voltage supply at the KPS terminals to ensure it provides the rated voltage of 27.1 V.
- 2
Check the power supply unit providing the 27.1 V for proper output.