PWR/1.2V Off (CIB_SR)

CIB_SR 1.2V Power Supply Not Present

Kuka · Sunrise Cabinet Med Controller

Hva betyr PWR/1.2V Off (CIB_SR) ?

The PWR/1.2V Green LED for the CIB_SR module is OFF, indicating a lack of 1.2V supply voltage to the module. This absence of critical operating voltage prevents the CIB_SR module from functioning correctly and could result in the non-operation of interconnected I/O nodes.

Vanlige årsaker

  • The 1.2V power supply to the CIB_SR module is not present.
  • The CIB_SR module requires 1.2V power, which is currently absent.
  • Failure or absence of the 1.2V power rail for the CIB_SR communication board.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check fuse F17.3 on the CCU_SR for continuity and proper rating.

  2. 2

    Verify the presence and correct seating of jumper plug X308.

  3. 3

    Check fuse F308 on the CCU_SR for continuity and proper rating.

  4. 4

    If an external supply is used via X308, check the external power supply to ensure it provides the rated voltage of 24 V.