PWRS/3.3V Off

CCU_SR Safety Power Supply Not Present

Kuka · Sunrise Cabinet Med Controller

Hva betyr PWRS/3.3V Off ?

The PWRS/3.3V Green LED is OFF, indicating an absence of supply voltage for the safety-related 3.3V rail. This condition points to a power supply issue to the CCU_SR module or a fault within the module itself, specifically impacting critical safety functions that rely on this voltage.

Vanlige årsaker

  • The safety power supply (PWRS/3.3V) for the safety circuit is not present.
  • The 3.3V power rail dedicated to safety functions is off.
  • Loss of power to the safety control unit (CCU_SR) safety supply.

Reparasjonssteg & Sjekkliste

Klikk på steg for å spore fremgangen.

  1. 1

    Check fuse F17.3 on the CCU_SR for continuity and proper rating.

  2. 2

    If the PWR/3.3V LED (Item 6) lights up, indicating the main 3.3V power is present, but the PWRS/3.3V is off, exchange the CCU_SR module as the safety power rail is internally faulty.